It is a hot evening, and you are reading in the living room with one lamp on. Somewhere outside, the air conditioner clunks and hums awake. For half a second the lamp sags, as if the house took a breath, and then it steadies. Most people never say anything about it. They glance up, shrug, and go back to the page. But that small sag is the house telling you something true: the wires in the walls are not an infinite well of power. They are a shared, imperfect road, and for a moment someone else took all the lanes.
The moment a motor wakes up
An air conditioner's compressor is an induction motor, and induction motors have an awkward secret. While running, a motor spins and generates a back-voltage, called back-EMF, that opposes the incoming current and holds it to a modest level. At the instant of startup, the rotor is standing still. There is no back-EMF yet. The windings behave like little more than a coil of copper, and the motor gulps current until it speeds up.
This is called locked-rotor or inrush current. For a typical single-phase compressor it can be several times the running current. The nameplate on the outdoor unit lists both a running figure (RLA) and a locked-rotor figure (LRA). That gap is the whole story. For a fraction of a second, up to a second or so, your house is asking the utility for far more current than the unit ever draws once it settles.
Where the voltage actually goes
Here is the part that surprises people. The lights don't dim because the power runs out. They dim because voltage is lost along the way.
Every conductor between the transformer and your lamp has a little resistance. When current flows through resistance, some voltage is dropped across it, following Ohm's law: volts lost equals current times resistance. Your lamp only gets what is left over.
Take an illustrative example. Say the service conductors and the utility transformer together present about 0.05 ohm of resistance to the loop. With a quiet house drawing 20 amps, you lose about 1 volt, which nobody notices. Now the compressor starts and pulls an extra 100 amps for a moment. That adds roughly 5 more volts of loss, so a 120-volt supply briefly reads closer to 114. These numbers are made up for the sake of the arithmetic, and your own house will differ. But the mechanism is real, and it is the same voltage drop the code worries about in long feeders, only here it plays out in time rather than distance.
The key insight is that the drop is shared. The lamp in the living room is on the same service as the compressor, so it sees the dip too, even though it is on a different breaker. Separate branch circuits give you separate wiring, but they do not give you separate sources. Everything meets at the panel, and the panel meets the service.
Why your eyes catch it so easily
A 5% sag sounds trivial. It does not look trivial, for two reasons.
First, an incandescent filament is a steep curve. A common engineering rule of thumb is that light output changes roughly with the 3 to 4 power of voltage, so a few percent of voltage translates into several times that in brightness. A drop that costs the wiring 5% can cost an old-style bulb something like a fifth of its light.
Second, human vision is remarkably sensitive to sudden change. Your visual system is built to notice motion and flicker at the edge of your attention, and it is especially touchy to fluctuations in the range of several cycles per second. A single sag does not need to be big to register. It only needs to be abrupt.
This is also why LED bulbs behave differently. Their drivers regulate internally and often smooth out small dips, so many homes with LEDs notice the flicker less, or notice a different symptom, such as a quick twitch instead of a slow sag. Cheap drivers can do the opposite and make the flicker worse. If your lights changed to LED and the dimming vanished, the wiring did not get better. The bulbs just stopped showing it.
Normal quirk or warning sign?
A brief, mild dip when a big motor starts is usually just physics. Refrigerators, well pumps, washing machines, garage-door openers and air compressors all do it. But the same symptom can come from a few different causes, and they deserve different responses.
Likely harmless: the dip lasts well under a second, it is the same every time, and it shows up in all the lights about equally. That points to the normal source impedance of your service and the utility transformer.
Worth a closer look: the dip is deep, lasts several seconds, or the compressor struggles to start and trips its breaker. A compressor stuck near its locked-rotor current is overheating its windings. A failing start capacitor is a common cause, and it is a cheap part that saves an expensive motor.
Call an electrician promptly: some lights get brighter while others dim, lights flicker without any big appliance starting, or you notice a buzzing, a warm panel, or a burning smell. Brightening on one leg while another dims is the classic signature of a failing or loose neutral on the service, because the voltage between the two legs is no longer dividing evenly. That is a fault, not a quirk. Overheating at a loose connection can start a fire, and it can also destroy electronics at both ends of the imbalance.
What actually fixes it
The fix depends on the cause, and the options run from cheap to substantial.
- A soft starter limits the inrush by ramping the motor up gradually. Aftermarket soft-start kits for residential compressors exist and can cut the startup surge considerably.
- A variable-speed or inverter-driven unit avoids the surge almost entirely, because it never slams the motor across the line at full voltage.
- A healthy start or run capacitor helps the motor accelerate quickly, shortening the duration of the dip.
- Tightening or replacing a bad connection in the panel, meter base, or service entrance, which is a job for a qualified electrician, removes unnecessary resistance that makes every dip worse.
- A larger service conductor or a closer transformer, arranged through the utility, lowers the source impedance for the whole house.
Notice what is not on the list: moving the lamp to a different circuit. It will not help, because the sag happens upstream of the branch.
Your next moves
- Read the nameplate. Go outside to the condenser and find the RLA and LRA on the data label. Divide LRA by RLA to see how hard your unit kicks at startup.
- Time the dip. Next time it happens, count it. Under a second is typical. Several seconds, or repeating starts, is not.
- Watch which lights react. Note whether every light dims together, or whether some brighten as others dim. Brightening on one side is your cue to call a pro and to stop using sensitive electronics until it is checked.
- Check the panel by feel and by eye. With the cover on, touch the outside of the panel and meter base. Unusual warmth, discoloration, or a faint buzz means a connection needs attention. Do not open the panel yourself.
- Ask about a capacitor and a soft start. If the unit is hard-starting, have an HVAC technician test the capacitor and quote a soft-start kit before you consider replacing the whole system.
A small sag, honestly measured
The nice thing about this question is that it can be answered with arithmetic instead of guesswork. Current times resistance gives you the drop, and the drop gives you the dip. Voltly's voltage drop and ampacity calculators are built for exactly that kind of what-if, offline, right where you're standing. If you want to see how a conductor's size and length change the number, you can try it at https://voltly.lumenlabs.works.